Model: 1621-KIT
The kit includes the earth ground tester which is the first line of defense in detecting reliable ground connections. Additionally, the unit features basic ground testing methods including 3-pole Fall-of-Potential as well as 2-pole ground resistance. It also inludes cables and ground stakes.
Discontinued!
This product has been discontinued and is no longer available.
This is the direct replacement:
Its convenient size, rugged holster, and large, clear LCD display make it an ideal field earth ground tester, for most electrical grounding work environments. With a simple user interface and intuitive functionality, the kit is a handy grounding tool for electrical contractors, utility test engineers, and earth ground specialists.
Features
| General Specifications | |
| Measuring Functions | 3-pole earth ground resistance, 2-pole AC resistance of a conductor, interference voltage |
| Intrinsic Error | Refers to the reference temperature range and is guaranteed for one year |
| Measuring Rate | 2 measurements/second |
| Battery1 | One 9 volt alkaline (LR61) |
| Battery condition | LO-BAT is displayed if voltage drops below 6.5 V |
| Voltages | Between jacks H/C2 and E/C1: 250 Veff maximum (effective voltage) |
| Between jacks S/P2 and E/C1 | 250 Veff maximum |
| Climatic Class | VDE/VDI 3540 RZ (conforming to KWG as per DIN 40040, 4/87) |
| Temperature Performance2 | Working: 14 to 122°F (-10 to 50°C) |
| Operating | 32 to 95°F (0 to 35°C) |
| Storage | 68 to 140°F (-20 to 60°C) |
| Reference | 73°F ±4°F (23°C ±2°C) |
| Temperature Coefficient | ±0.1% of range per degree Kelvin |
| Safety | IEC/EN 61010-1, 600 V CAT II, pollution degree 2 |
| Maximum Deviations | |
| E1Influence Factor | Position |
| E1 Deviation Influence | 0% |
| E2 Influence Factor | Supply voltage |
| E2 Deviation Influence | 0% |
| E3 Influence Factor | Temperature E3 |
| E3 Deviation Influence | 0.23% |
| E4 Influence Factor | Serial interference voltage (20 V) |
| E4 Deviation Influence | 0.6% |
| E5 Influence Factor | Probe and auxiliary probe resistance |
| E5 Deviation Influence | 10% |
| Electrical Information | |
| Test Voltage | 3.7 kV |
| Protection Type | IP 40; IEC/EN 60529 |
| Electromagnetic Compatibility | Emission: IEC/EN 61326 Class B |
| Immunity | IEC/EN 61326 Annex C |
| RE Resistance Measurement | Measuring method: Current-voltage measurement with improved cross-talk attenuation, no compensation of measuring lead resistance, with probe (3-pole) or without probe (2-pole), as per IEC/EN 61557–5 |
| Open Circuit Voltage | 23 to 24 V AC |
| Short Circuit Current | >50 mA AC |
| Measuring Frequency | 128 Hz |
| Maximum Permissible Overload | 250 Veff |
| Measuring Time | 8 seconds (average from when START is pressed) |
| Limit Input | Tester retains set value even if instrument is turned off (assuming battery power supply is sufficient) |
| Automatic Changeover of Resolution | RH <7 kΩ |
| Resolution | 0.01 Ω |
| RH | <50 kΩ |
| Resolution | 0.1 Ω |
| RH | >50 kΩ |
| Interference Voltage Display DC + AC | Vmax 30 Veff |
| Common Mode Rejection | >80 dB at 50 Hz and 60 Hz |
| Measuring Uncertainty | <10% for pure AC and DC signals |
| Measuring Range | |
| Resolution | 0.15 Ω to 20 Ω |
| Display range | 200 to 1999 Ω |
| Intrinsic Uncertainty | ±(6% of measured value + 5D) |
| Operating Uncertainty IEC 615573 | ±(18% of measured value + 5D) |
| Dimensions | 4.5 x 2.1 x 8.5" (113 x 54 x 216 mm), including holster |
| Weight | 1.9 lbs (850 g), including standard accessories, volume approximately 600 cm3 |
Click on a category to view a selection of compatible accessories with the Fluke 1621 Earth Ground Tester Kit.